Laserfiche WebLink
111 1100 Field Test Apparatus Page 1 of 1 <br />a4 Tanknoiogy Line Leak Detector Test <br />Work Order: 2304275 Date: 6/21/2012 <br />Site Name / ID: VALERO 3641 / 3641 <br />Address: 1210 E. HAMMER LANE @ WEST LANE <br />City: STOCKTON State: CA Zip: 95210 <br />Tank ID <br />T1 T2 <br />T3 <br />T1 <br />Product <br />UNLEADED Enhanced <br />PREMIUM <br />UNLEADED <br />Product Line <br />1 1 <br />1 <br />1 <br />Tested From <br />5 5 <br />5 <br />5 <br />Existing/New <br />Existing Existing <br />Existing <br />Existing <br />Mechanical/Electronic <br />Mechanical Mechanical <br />Mechanical <br />Mechanical <br />Manufacturer/Model <br />Red Jacket FX1V Red Jacket FX1V <br />Red Jacket FX1V <br />Red Jacket FX1 <br />Serial No. <br />40602-0233 10602-0193 <br />40906-8487 <br />40602-0233 <br />Pump Operating Pressure (psi) <br />45.00 39.00 <br />39.00 <br />45.00 <br />Calibrated Leak (mi/min) <br />189.0 189.0 <br />189.0 <br />189.0 <br />Calibrated Leak (gph) <br />3.00 3.00 <br />3.00 <br />3.00 <br />Holding PSI <br />"NIA for Electronic Lo's <br />40.00 19.00 <br />13.00 <br />40.00 <br />Resiliency (ml) <br />N/A for Electronic LD's <br />3000.00 1950.00 <br />1820.00 <br />1150.00 <br />Metering PSI <br />`N/A for Electronic LD's <br />13 <br />12 <br />11 <br />Opening Time (sec) <br />'N/A for Electronic LD's <br />34 <br />53 <br />10 <br />Test Results <br />Pass <br />Pass <br />Pass <br />Technician Comments: had to purge lines in order to achieve passing LD results. <br />Technician Name: Kristopher Bell <br />Technician Signature: <br />Environmental Compliance for Petroleum Systems <br />® 2010 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com <br />Certification #: 1324 <br />