Laserfiche WebLink
e � <br />4. Spill/Overfill Containment Boxes <br />Test Method Developed By: ❑ Tank Manufacturer 0 Industry Standard ❑ Professional Engineer <br />Test Method Used: ❑ Pressure ❑ vacuum N Hydrostatic <br />Test Equipment Used: Incon TS STS Leak Detector Equipment Resolution: ±0.002 <br />Comments: A 1 hour lake test was performed on all three spill buckets. All measurements were taken from the top of the fill cap. <br />2 of 2 <br />Spill Box # 87 I <br />Spill Box # 89 I <br />Spill Box # 91 <br />I Spill Box # <br />ucket Diameter. <br />Bucket Depth: <br />14" <br />14" <br />14" <br />Wait time: <br />15 min <br />15 min <br />15 min <br />Test Start Time: <br />1:40 <br />1:40 <br />1:40 <br />Initial Reading: <br />2 1/4" <br />1 1/2" <br />2 5/8" <br />Test End Time: <br />2:40 <br />2:40 <br />2:40 <br />Final Reading: <br />2 1/4" <br />1 1/2" <br />2 518" <br />Test Duration (hh:mm) : <br />01:00 <br />01:00 <br />01:00 <br />00:00 <br />Change in Reading: <br />0.0000 <br />0.0000 <br />0.0000 <br />0.0000 <br />Pass/Fail Threshold or Criteria: <br />±0.002 <br />� <br />±0.002 <br />+0.002 <br />I <br />+0.002 <br />Test Result: <br />*Pass O Fail i <br />*Pass O Fail j <br />*Pass O Fail <br />Comments: A 1 hour lake test was performed on all three spill buckets. All measurements were taken from the top of the fill cap. <br />2 of 2 <br />