Laserfiche WebLink
4. Spill/Overfill Containment Boxes <br />Test Method Developed By: ❑ Tank Manufacturer <br />Test Method Used: ❑ Pressure <br />Test Equipment Used: Incon TS STS Leak Detector <br />❑X Industry Standard ❑ Professional Engineer <br />❑ vacuum ❑X Hydrostatic <br />Equipment Resolution: ±0.002 <br />Comments: 91 spillbox was replaced on this day prior to testing. <br />2 of 2 <br />Spill Box # 87 <br />Spill Box # 89 <br />Spill Box # 91 <br />Spill Box # <br />Bucket Diameter: <br />Bucket Depth: <br />14" <br />14" <br />14" <br />Wait time: <br />15 min <br />15 min <br />15 min <br />Time: <br />Flnitial <br />8:52 AM <br />8:52 AM <br />9:33 AM <br />ding: <br />5.7723 <br />6.9216 <br />5.8845 <br />esnd Time: <br />9:07 AM <br />9:07 AM <br />9:48 AM <br />Final Reading: <br />5.7721 <br />6.9211 <br />5.8839 <br />Test Duration (hh:mm) : <br />00:15 <br />00:15 <br />00:15 <br />00:00 <br />Change in Reading: <br />-0.0002 <br />-0.0005 <br />-0.0006 <br />0.0000 <br />Pass/Fail Threshold or Criteria: <br />±0.002 <br />±0.002 <br />±0.002 <br />±0.002 <br />Test Result: <br />O Pass Q Fail <br />QQ Pass O Fail <br />® Pass Q Fail <br />Comments: 91 spillbox was replaced on this day prior to testing. <br />2 of 2 <br />