Laserfiche WebLink
Test Method Developed By: <br />Ll <br />4. Spill/Overfill Containment Boxes <br />❑ Tank Manufacturer <br />Test Method Used: ❑ Pressure <br />Test Equipment Used: Incon TS STS Leak Detector <br />11 <br />0 Industry Standard ❑ Professional Engineer <br />❑ vacuum N Hydrostatic <br />Equipment Resolution: ±0.002 <br />Comments: <br />2 of 2 <br />[Spill Box # 87 <br />Spill Box # 89 <br />Spill Box # 91 <br />Spill Box # <br />ucket Diameter: <br />Bucket Depth: <br />14" <br />14" <br />14" <br />Wait time: <br />15 min <br />15 min <br />15 min <br />Test Start Time: <br />1:05 PM <br />12:01 PM <br />12:21 PM <br />Initial Reading: <br />4.4557 <br />2.1732 <br />4.5980 <br />Test End Time: <br />Final Reading: <br />Test Duration (hh:mm) : <br />Change in Reading: <br />1:20 PM <br />4.4554 <br />00:15 <br />-0.0003 <br />12:16 PM <br />2.1727 <br />00:15 <br />-0.0005 <br />12:37 <br />4.5998 <br />00:16 <br />0.0018 <br />00:00 <br />0.0000 <br />Pass/Fail Threshold or Criteria: <br />±0.002 <br />±0.002 1 <br />±0.002 <br />±0.002 <br />Test Result: <br />*Pass 0 Fail <br />0 Pass O Fail <br />Pass Fail <br />Comments: <br />2 of 2 <br />