Laserfiche WebLink
4. Spill/Overfill Containment Boxes <br />t <br />Test Method Developed By: ❑ Tank Manufacturer ❑X Industry Standard <br />Test Method Used: ❑ Pressure ❑vacuum <br />Test Equipment Used: Incon TS STS Leak Detector <br />❑ Professional Engineer <br />❑X Hydrostatic <br />Equipment Resolution: #0.002 <br />encs: <br />Replaced and tested 91 spillbox <br />Spill Box # 91 <br />Spill Box # <br />Spill Box # <br />Spill Box # <br />Bucket Diameter: <br />11" <br />Bucket Depth: <br />18" <br />Wait time: <br />15 min <br />15 min <br />15 min <br />15 min <br />Test Start Time: <br />11:56am <br />Initial Reading: <br />7.1919 <br />Test End Time: <br />12:11 pm <br />Final Reading: <br />7.1911 <br />Test Duration (hh:mm) : <br />00:15 <br />00:00 <br />00:00 <br />00:00 <br />Change in Reading: <br />-0.0008 <br />0.0000 <br />0.0000 <br />0.0000 <br />Pass/Fail Threshold or <br />Criteria: <br />±0.002 <br />#0.002 <br />±0.002 <br />±0.002 <br />Test Result: <br />Pass O Fail O NA <br />O Pass O Fail O NA <br />O Pass O Fail O NA <br />O Pass O Fail O NA <br />encs: <br />Replaced and tested 91 spillbox <br />