The fittings listed and illustrated here are common examples of what may be installed in your Bravo <br />B-2000 series shallow steel UDC's. In many cases entry fittings were used for pipe or conduit that they <br />were not designed for. Read every scenario below as there are valuable tips, warnings and <br />instructions. Some may apply broadly. Bravo does not make any requirements for which combinations <br />are acceptable, nor does Bravo specify any heights, elevations or measurements for adjustments. <br />11 - <br />FR -ESI RETROFIT <br />FEF -EBS CONDUIT FITTING <br />For this fitting, remove the existing boot & clamps, clean the <br />contact surfaces of any/all contaminants, abrade the contact <br />surfaces of both pipes and install the FR-ES1 split FRP sleeve <br />centered over both diameters. You can pack the interior of the <br />steel coupler with foam cord or other material first. Then pack <br />each half with Bravo epoxy, join them together and secure with <br />clamps to cure. Bead with Epoxy where it contacts the floor. <br />FR-MYE-5 RETROFIT <br />MYERS HUB (MYE) CONDUIT <br />FITTING For MYE's, clean the exterior of the fitting <br />and sand the epoxy paint off of the steel floor about 1" out <br />from its outer diameter. Apply Bravo epoxy to interior of <br />FR-MYE-5 split FRP sleeve and install over the MYE fitting <br />with clamps. Ensure it is completely encapsulated with no <br />trapped air. Then apply a generous bead of vulkem to the <br />outside of the FRP sleeve where it contacts the floor. Be <br />sure to re -coat any steel that was exposed from sanding / <br />cleaning. Just above it, where commonly another pipe <br />protrudes through and a conduit comes through that pipe, <br />follow the FR-ES1 retrofit directions above to seal these <br />two pipes to each other. <br />BH -1-1/2 VAPOR FITTING <br />Clean the exterior surfaces of the fitting and repeal: the <br />instructions listed above for the Myers Hub fitting. It is <br />common for a vapor shear valve to be threaded directly <br />onto this type of fitting. If so, then the FR-MYE-5 should <br />apply, but if there is a nipple above, then the FR-ES1 may <br />also be needed. It is detailed below and shown on the left. <br />In the case where this fitting was instead used as a conduit <br />entry, (as shown) first install the FR-ES1 to the top -most <br />part of the threads and the conduit that protrudes through. <br />2 ii -B2000 -RETROFIT -KIT -14A <br />