Laserfiche WebLink
i s <br /> RECEIVED <br /> SEP 0 2018 <br /> 5 <br /> 7. UNDER-DISPENSER CONTAINMENT UDC TESTIN <br /> Test Method Developed By: ❑UDC Manufacturer ®Industry Standard ❑Professi rrT79=r <br /> WhM03MMES <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ®Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Incon Sump Tester Equipment Resolution: +/.0.002 Inches <br /> UDC# 1/2 UDC# 5/6 UDC# UDC# <br /> UDC Manufacturer: Bravo Bravo <br /> UDC Material: steel steel <br /> UDC Depth: 101, 10" <br /> Height from UDC Bottom to Top 1130ttom Bottom <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to Bottom Bottom <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to <br /> testing., <br /> Good Good <br /> Portion of UDC Tested 2"Above Piping 2 Above Piping <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both N/A NIA <br /> product and water)?* <br /> Turbine shutdown response time N/A N/A NIA N/A <br /> Is system programmed for fail- <br /> safe shutdown?' ❑Yes ❑No ®NA ❑Yes ❑No ®NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> Was fail-safe verified to be ❑yes ❑No p NA ❑Yes ❑No p NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> -starting test <br /> Test Start Time: 9:36 am 10:25 am <br /> Initial Reading(Rt): 3.5087 Inches 2.7664 Inches Inches Inches <br /> Test End Time: 9:51 am 10:40 am <br /> Final Reading(RF): 3.5067 Inches 2.7661 Inches Inches Inches <br /> Test Duration: 15 Minutes 15 Minutes <br /> -Change,in Reading(RF-RI): 0.0020 0.0003 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 <br /> Test Result: p Pass ❑Fail p Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail <br /> Was sensor removed for testing? ®Yes ❑No ❑NA ®Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> Was sensor properly replaced and ®Yes ❑No ❑NA ®Yes ❑No [INA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> verified functional after testin ? <br /> Comments—(include information on repairs made prior to testing,and recommended follow-up for failed tests) <br /> "Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment <br /> testing scope of work". <br /> Installed conduit boots in UDC 1/2 and 5/6. <br />