Laserfiche WebLink
UNDER DISPENSER CONTAINMENT (UDC) TESTING <br /> �1( � jf, .:. Manufacturer i fn77:7*7*7d�#stry S ndarct ,;p Profen r1al Engr. 0 Lather_(seebelow) :r. <br /> t: fQd:.. 51 St:;;:.. o Fres ute:<" . j v cuc tn.:........:. #� El�tdres a 0:::::0 theC(sed elsw <br /> .. .. <br /> Ilam r`rn ,Egli iprr�er a ;:. :v:::el Char ge to [tr t r <br /> .... { aldweI System 20 1!1Naiton Engfneer�ig) <br /> O.C. t.an:. . <br /> Evils ; }�2 <br /> UDC Manufacturer Bravo Bravo <br /> UDC Material Steel Steel <br /> UDC Depth(inches) <br /> Height from UDC bottom to highest Bottom Bottom <br /> 9 9 <br /> piping penetration <br /> Height from UDC bottom to lowest Bottom Bottom <br /> electrical penetration <br /> Condition of UDC prior to testing Dry ry D <br /> Portion of UDC tested Entire Entire <br /> Type of shut-down present Float Float <br /> `.Was sensor removed for testing? ......N/A N/A <br /> Was sensor properly replaced after testing? N/A N/A <br /> Wait time for water level to stabilize 0:10 0:10 <br /> Depth of water level from UDC bottom in. 6" <br /> ( ) 6" <br /> Test start time 10:00 AM 10:01 AM <br /> Test end time 10:30 AM 10:31 AM <br /> Test duration 0:30 0:30 <br /> Change in water level t 0.000 inches 0.000 0.000 <br /> Pass/Fail threshold(0.005 inches/h Hr. 0.005 0.005 <br /> TEST T <br /> S RESULT <br /> PASS PASS <br /> Comments: <br /> 0 2002 Walton Engineering,Inc. <br />