Laserfiche WebLink
0 <br /> Triangle Environmental In <br /> 2525 West Burbank Blvd.,Burbank,CA 91505-2302 <br /> (818)840-7020 (818)840-6929 <br /> LIST TESTING SYSTEMS SU MA R YS EET <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Tosco Marketing Co. TOSCO Facility # 05,14 /�7 <br /> 4 <br /> 1500 North Priest Drive <br /> Tempe, AZ 85281 'Test Date. 8/ 301 <br /> Kathy Strickland <br /> (602)728-7149 <br /> Facility: 2705447 Work#: 7405478 <br /> Tosco Facility#05447 County: SAN JOAQUIN <br /> 1469 E HAMMER LN Cross Street: E HAMMER LANE/WEST LANE <br /> STOCKTON, CA 95209 <br /> Tank Test System Tank Line <br /> # Product Capacity Type Rate/Results Ullage Result Rate/Result L/D Result <br /> 1 Unleaded Regular 12068 N/A N/A N/A PASS <br /> 2 Unleaded Premium 10583 N/A N/A N/A PASS <br /> 3 Unleaded Plus 10583 N/A N/A N/A PASS <br /> 4 Diesel 10583 N/A N/A N/A PASS <br /> Certified By: Technician: Steve Sweatt State Lic.#s: CA-1616 <br /> 3�� *7 Mfgr's#: TEI-056 <br /> Comments: <br /> Stage II A/L&pressure decay. Compliance L/D&monitor certification. <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd>95% and Pfa<5%as required by Local,State and Federal EPA UST Technical <br /> Standards Part 280 for precision testing systems. This SB-989 secondary containment testing system <br /> exceeds the criteria for detection as required by state and local agencies. <br />