Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: CO #00548 <br /> Tank : 4 Test ate: 2/ 5/97 <br /> Product: Unleaded Plus Work#: 340281 <br /> Test Method: System 4000 Test Method: R.J.FTA <br /> Capacity: 4000 Manufacturer: <br /> Diameter(in): 76 L/D Model: <br /> Product Level(in): 65 L/D Serial#: <br /> Liquid Volume(Gals): 3400 Line Drain Back(ml): <br /> Liquid Percent(%): 85.0% L/D Trip Time(sec): <br /> Specific Gravity: 0.750 Holding Pressure(psi): <br /> Coef.of Expansion: 0.000660 Metering Pressure(psi): <br /> Water On Tank(in): 0 L/D Test Rate(gph): <br /> Water In Tank(in): 0 L/D Result: N/A <br /> Product Temp. (F): 65 <br /> Head Pressure(psi): 1.8 <br /> Test Start Time: 8:30:00 AM Test Method: <br /> Test End Time: 11:00:00 AM <br /> Pump Brand: <br /> Test Rate(gph): -0.02 <br /> System Type: <br /> Test Result: PASS Line Pressure(psi): <br /> ONE : MINE IN i <br /> Line Start Time: <br /> Test Method: ULLAGE Line End Time: <br /> UllageVolume(gals.): 600 Line Start Level: <br /> Ullage Test Time: 12:05:00 PM Line End Level: <br /> Ullage Vacuum(psi): 1 Line Test Rate(gph): <br /> Ullage Result: PASS Line Test Result: N/A <br /> SLAVE TANK ON MANIFOLDED TANK. <br /> 5 <br />