Laserfiche WebLink
WESTERN AMERICA TANK TESTING, INC. A";, <br />I V <br />3131 Fairhaven Drive <br />Bakersfield, <br />MMBakersfield, CA 93308 <br />(805) 322-9827 ENVIRONMENTAL HEALTH <br />l <br />PERM IT/SERVICES <br />ANNUAL 3 --STEP RED JACKET LEAK DETECTOR TEST <br />OWNER QUIZ{ STOP MARKET #120 <br />LOCATION <br />Stockton, CA. <br />_� DATE <br />08/22/91 <br />PRODUCT: <br />Regular Unleaded, <br />Premium Unleaded, Diesel <br />(Circle one) <br />NOTE: Use separate form for- <br />each Tank. <br />(1) <br />Running Pressure. 26 <br />, (2) Shut -.-Off Pressure <br />_ 2-9 <br />(3) <br />Amount of Product Released thru <br />Bibcock to Zero <br />16 oz. <br />(4) <br />With Valve Open ---Start STP - <br />List: Pressure 4 <br />_P.S.I., <br />(5) <br />Reduce Flow to Rate of 7 oz. <br />per Minute - List Pressure at this Flow <br />Rate -----_ 10P.S.I., <br />(6) <br />Turn STP Off' - Let Pressure <br />drop to zero thru Leak just <br />created - List <br />time for Gauge to Reach Zero <br />_ mill. 45 <br />sec., <br />(7) <br />Turn the STY back on - Keep <br />Leak Rate at Bibcock - List. <br />pressure <br />10 P.S.I. - Flow <br />Rate at Nozzle _ 1.0 _ <br />G.F.M., <br />(8) <br />Stop Leak with STP still. on <br />- Does Leak Detector reset. <br />X _yes no <br />If yes - How long to reset <br />--min 4 sec., <br />(9) <br />Turn STP off - I.i.st pressure <br />22 _ P.S.I. , <br />(10) <br />Turn STP back on -• List time <br />to reach pressure rise <br />mill. 2 sec. <br />(11) List. Pressure <br />(12) Open Nozzle and List Pressure 20 P.S.I. <br />SATISFACTORY LEAK DETECTOR X _ _ Yes _ No. <br />LEAK DETECTOR <br />Model 116-030 +_ _��_, Date Code & Serial * 10288--2224 <br />