Laserfiche WebLink
r-1 <br />0 2015 Walton Engineering, Inc. <br />SECONDARY LINE TESTING <br />-mAY o 7 2015 <br />Test Method By: <br />O Manufacturer <br />• Industry Standard o Professional Engr o Other (see below) <br />Test Method Uses: <br />• Pressure <br />o vacuum o Hydrostatic <br />o Other (see below) <br />Measuring Equipment Used: <br />Pressure Gauge (range 0 to 15 prig) <br />Description <br />Line #1 <br />Line #2 <br />Tank product <br />Gasoline - 91 <br />Gasoline - 87 <br />Pipe manufacturer <br />Smith <br />Smith <br />Pipe material <br />FRP <br />FRP <br />Primary pipe diameter (inches) <br />2 <br />2 <br />Secondary pipe diameter (inches) <br />3 <br />3 <br />Method of secondary pipe isolation <br />Termination Boot <br />Termination Boot <br />Location of secondary pipe isolation <br />Sump <br />Sump <br />Estimated length of piping run (feet) <br />45 <br />55 <br />(include length of branch runs) <br />Wait time for pressure to stabilize (hr:min) :10 <br />:10 <br />Test start time <br />9:40 AM <br />9:42 AM <br />Initial pressure (psig) <br />5.0 <br />5.0 <br />Test end time <br />10:40 AM <br />10:42 AM <br />Final pressure (psig) <br />5.0 <br />5.0 <br />Test duration (hr:min) <br />1:00 <br />1:00 <br />Change in pressure (psig) <br />0.0 <br />0.0 <br />Pass/Fail threshold (psig) <br />0.5 <br />0.5 <br />TEST RESULT <br />PASS <br />PASS <br />Comments: <br />0 2015 Walton Engineering, Inc. <br />