Laserfiche WebLink
.7 <br />Ll <br />SWRCB, January 2002 Page of <br />17. FILL RISER CONTAINMENT SUMP TESTING <br />Facilitv is Not Eauioned With Fill Riser Containment Sumns ❑ <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Sump Manufacturer ❑ Industry Standard X Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum X Hydrostatic <br />❑ Other (Snecifv) <br />Test Equipment Used: Caldwell Level Change Indicator <br />Em <br />Fill Sump#5-Diesel- Fill Sump # <br />A -B <br />Sump Diameter: 42" <br />Equipment Resolution: .002 <br />Fill Sump # Fill Sump # <br />Sump Depth: 44" <br />Height from Tank Top to Top of No Piping <br />Highest Piping Penetration: Penetrations <br />Height from Tank Top to Lowest 14" <br />Electrical Penetration: <br />Condition of sump prior to Dry <br />testing: <br />Portion of Sump Tested Water Line 16" <br />Sump Material: Fiberglass <br />Wait time between applying 5 Minutes <br />water and starting test: <br />Test Start Time: 1:55 <br />Initial Reading (RI): .001 <br />Test End Time: 2:25 <br />Final Reading (RF): .001 <br />Test Duration: 30 Minutes <br />Change in Reading (RF—RI): 0 <br />Pass/Fail Threshold or Criteria: .005/30 Minutes <br />Tes exult: <br />Is there a sensor in the sump? Yes <br />Does the sensor alarm when <br />either product or water is Yes <br />detected? <br />Was sensor removed for testing? Yes <br />Was sensor properly replaced and Yes <br />verified functional after testin . <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />