Laserfiche WebLink
SPILL CONTAINER TEST R ORT <br />TEST DATE: January 4, 2006 <br />1. OWNER <br />Name Bonfare Markets, Inc. <br />Address 25064 Viking Street Hayward, CA 94545 Phone # 510-732-5700 <br />Contact Milt DeLac <br />2. FACILITY <br />Name Bonfare Market # 35 <br />Address 15 W. Grant Line Rd. Tracy, CA 95376 Phone # 510-732-5700 <br />Contact Milt DeLac <br />3. CUPA <br />Name San Joaquin County Environmental Health Notified January 3, 2006 <br />Address 304 E Weber Avenue 3rd Floor Stockton, CA 95202 Phone # 209-468-9847 <br />Contact Tank Team Fax# 209-468-3433 <br />Inspector Present Lori Luces <br />4. TESTING CONTRACTOR <br />Name Walton Engineering, Inc. Lic# 617238 A, B, Haz <br />Address P.O. Box 1025, West Sacramento, CA 95691 Phone # 916-373-1152 <br />Contact Michael Walton Fax# 916-373-1172 <br />Test Technician Isaac Diaz <br />5. TEST RESULTS <br />(measuring equipment usea: uaiaweu system zuui / vvalton tnglneering (Level unange I <br />Description Tank #1 Tank #2 Tank #3 <br />Product contained <br />Gasoline - 91 <br />Gasoline - 87 slave <br />Gasoline - 87 Master _ <br />Spill container capacity (US gallons) <br />5 <br />5 <br />5 <br />Spill container manufacturer <br />DPW <br />OPW <br />OPW <br />Spill container depth (inches) <br />13.75 <br />13.00 <br />13.00 <br />Is the spill container located in a sump? <br />Yes <br />Yes <br />Yes <br />Does sump have a liquid sensor installed? <br />Yes <br />Yes <br />Yes <br />Condition of spill container prior to testing <br />Dry <br />Dry <br />Dry <br />Portion of spill container tested <br />Entire <br />Entire <br />Entire <br />Depth of water level from bottom (inches) <br />13.50 <br />Wait time for water level to stabilize (hr:min) <br />Test start time <br />0:10 <br />11:45 AM <br />Test end time <br />12:15 PM <br />Test duration (hr:min) <br />0:30 <br />Change in water level (t 0.000 inches) <br />0.000 <br />Pass/Fail threshold (0.005 inches /'/z Hr.) <br />0.005 <br />TEST RESULT <br />PASS <br />6. COMMENTS <br />This is a retest after spill container replacement. <br />Technician Signature <br />Date <br />