Laserfiche WebLink
• Page 2 July 17, 1992 <br />ACCURACY AND RESPONSE <br />u <br />Monitor = <br />Veeder-Root UST Monitoring System: Model ILS 350 <br />NA -not applicable <br />Sensor. <br />Interstitial liquid sensor for fiberglass tanks 0794390-401 <br />NR -no response <br />Probe Size = <br />3.45:k 0.01 (" X 5.65 i 0.07 (L) X 1.90 t 0.05 (H) cm <br />Minimum Sensitive Height = 0.8 In (20 mm) + 20'/o = 24 mm <br />TEST PRODUCT = UNLEADED GASOLINE <br />Test Distance =12 ft <br />Liquid <br />Response <br />Recovery <br />Product <br />Liquid <br />Trial# <br />Probe# <br />Temp. <br />Time <br />Time <br />Activation <br />Flow Rate <br />Volume <br />°C <br />min <br />min <br />He' ht cm <br />ml/min. <br />ml <br />1 <br />31 <br />21.0 <br />3.67 <br />< 1 <br />1.3 <br />12.5 <br />46 <br />2 <br />31 <br />21.0 <br />3.43 <br />< 1 <br />1.2 <br />12.8 <br />44 <br />3 <br />31 <br />21.0 <br />3.42 <br />< 1 <br />1.3 <br />12.6 <br />43 <br />4 <br />31 <br />21.0 <br />3.35 <br />< 1 <br />1.2 <br />12.8 <br />43 <br />5 <br />31 <br />21.0 <br />3.42 <br />< 1 <br />1.3 <br />12.9 <br />44 <br />6 <br />31 <br />21.0 <br />3.40 <br />< 1 <br />1.3 <br />12.9 <br />44 <br />Averacie <br />3.45 <br /><1 <br />1.27 <br />12.8 <br />44 <br />Std. Dev. <br />0.11 <br />NA <br />0.05 <br />0.2 <br />1 <br />Detection Accuracy % <br />100.0 <br />Calculated Lower Detection Limit <br />Product Activation Height cm <br />1.65 <br />Camegie Mellon Research Institute 4400 Fath Ave. Pittsburgh, PA 15213 <br />