Laserfiche WebLink
0 Page 2 July 17, 1992 <br />ACCURACY AND RESPONSE <br />0 <br />Monitor - <br />Veeder-Root UST Monitoring System: Model ILS 350 <br />NA -not applicable <br />Sensor. <br />Interstitial liquid sensor for steel tanks 0794390-420 <br />NR -no response <br />Probe Diameter - <br />3.77 cm; Std. Dev.. 0.01 <br />Minimum Sensitive Height =1.6 in (40 mm) + 20°%o = 48 mm <br />TEST PRODUCT = UNLEADED GASOLINE <br />Test Distance .16 ft <br />Liquid <br />Response <br />Recovery <br />Product <br />Liquid <br />Trial#k <br />Prot" <br />Temp. <br />Time <br />Time <br />Activation <br />Flow Rate <br />Volume <br />min <br />min <br />He' ht cm <br />ml/min. <br />mi <br />1 <br />21 <br />22.1 <br />6.50 <br />< 1 <br />3.5 <br />7.7 <br />50 <br />2 <br />21 <br />22.1 <br />6.50 <br />< 1 <br />3.6 <br />7.8 <br />51 <br />3 <br />21 <br />22.0 <br />6.43 <br />< 1 <br />3.6 <br />7.8 <br />50 <br />4 <br />21 <br />22.0 <br />6.47 <br />< 1 <br />3.6 <br />7.7 <br />50 <br />5 <br />21 <br />22.0 <br />6.60 <br />< 1 <br />3.7 <br />7.6 <br />so <br />6 <br />21 <br />22.0 <br />6.57 <br />< 1 <br />3.7 <br />7.8 <br />51 <br />Avereae <br />6.51 <br /><1 <br />3.62 <br />7.7 <br />50 <br />Std. Dev. <br />0.06 <br />NA <br />0.08 <br />0.1 <br />1 <br />Detection Accuracy % <br />100.0 <br />Calculated Lower Detection Limit <br />Product Activation Hei ht cm <br />4.17 <br />Camegie Mellon Research Institute 4400 Fifth Ave. Pittsburgh, PA 15213 <br />