Laserfiche WebLink
0 <br />Liquid -Phase Product Detector Models TLS -350 & ILS -350 with <br />Version Groundwater Sensor (Form #7_qMO-621--622--624) <br />• <br />Evaluation Results (continued) <br />> Compiled Test Results (for tests conducted with 0.32 cm of floating product) <br />im <br />Accuracy (%) <br />Bias' (%) <br />Precision* (%) <br />Detection Time (hh:mm:ss) <br />• ��• <br />Fall Time (hh:mm:ss) 00:54:50 <br />Lower Detection Limit (cm) 0.02 <br />* Not applicable to qualitative detectors. <br />> Specificity Results (°�) <br />Commercial gasoline <br />Synthetic gasoline <br />Diesel fuel <br />Jet -A jet fuel <br />n -Hexane <br />Toluene Activated <br />Xylene(s) Activated <br />> Safety disclaimer: This test procedure only addresses the Issue of the method's <br />ability to detect leaks. It does not test the equipment for safety hazards. <br />Certification of Results <br />I certify that the liquid -phase product detector was operated according to the vendor's <br />instructions and that the evaluation was performed according to the standard EPA test <br />procedure for liquid -phase out -of -tank prpduct detectors except as noted on any attached <br />sheets. I also certify that the results presented above are those obtained during the evaluation. <br />Marc Portnoff <br />(printed name) <br />7';1a.w, L <br />_4 <br />(signature) IF <br />June $0. 1997 <br />(date) <br />Carnegie Mellon Research Institute <br />(organization performing evaluation) <br />Pittsburgh. PA 15230 <br />(city, state, zip) <br />(phone number) <br />* Consultant to the Manufacturer <br />Liquid -Phase Product Detector • Results Form Page 2 of 2 <br />