�s t <br /> D. Results of Testing/Servicing <br /> Software Version Installed: 16.5 <br /> Complete the following checklist: <br /> �✓ Yes No' Is the audible alarm operational? <br /> ❑✓ Yes ❑ No' Is the visual alarm operational? <br /> Ye, ✓ No' Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> Yes 1771 No" Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their <br /> proper operation? <br /> Yea No' If alarms are relayed to a remote monitoring station,is all communications equipment(e.g.modem)operational? <br /> WA <br /> Yes No' For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system <br /> NIA detects a leak,fails to operate,or is electrically disconnected? If yes:which sensors initiate positive shut-down? (Check all that apply) <br /> ❑Sump/Trench Sensors; ❑Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor <br /> failureidisconnection? Yes;JjNo. <br /> Yes ® No' For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e. no mechanical overfill prevention <br /> ✓ NIA valve is installed),is the overfill warning plarm vWyle and audible at the tank fill point(s)and operating properly? If so,at what percent <br /> of tank capacity does the alarm trigger? <br /> ❑ Yes' Q No Was any monitoring equipment replaced. If yes, identify specific sensors, probes, or other equipment replaced and list the <br /> manufacturer name and model for all replacement parts in Section E,below. <br /> E] Yes' n No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)©Product;©Water. If <br /> es,describe causes in Section E,below. <br /> ✓ YesT7 No' Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> IL✓ Yes No' Is all monitoring equipment operational per manufacturer's specifications? <br /> "to Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: <br /> At this time only the H5 fuel polisher sensor was tested, and confirmed operational. The fuel <br /> polisher is equipped with a generic sensor which is not operating, However this sensor is not <br /> part of the monitoring system as it is a stand alone sensor which does not communicate with <br /> the Veeder Root in any way. This was explained to inspectorCesar Ruvalcaba. <br /> Monitoring System Certification Page 2 of 4 12107 <br /> 7 <br /> 2/21/07 <br />