Laserfiche WebLink
9 0 <br /> E. Reporting format for Monitoring: <br /> Check TLS console for alarm status and enter findings in <br /> log book. A warning is indicated by a yellow light and <br /> buzzer, this indicates problems in the tank. An alarm is <br /> indicated by a red light and a buzzer, this is a serious <br /> problem and the following people must be called. If alarm <br /> sounds, call John Kim. If he is not available call Shaw's <br /> Maintenance at (209)668-8436. <br /> F. Preventative maintenance schedule for monitoring <br /> equipment: <br /> Yearly maintenance is required and will be performed by <br /> Shaw's Maintenance (209)668-8436, a factory trained and <br /> certified company, and is to include the following: <br /> TLS 350 Console: <br /> 1 . Check printer for paper. <br /> 2. Check display for "ALL FUNCTIONS NORMAL" <br /> message. <br /> 3. Print out TLS inventory to verify actual inventory. <br /> 4. Print out TLS setup values, then verify if backup battery <br /> is working. <br /> 5. Press Ala /Test button to verify power, warning and <br /> alarm indicators light and audible alarm sounds. <br /> MAG I Probes: <br /> 1 . Inspect probe cables for any cracking or swelling and <br /> replace as necessary. <br /> 2. Inspect floats and probe shafts for any residue buildup. <br /> Clean as necessary. <br /> 3. Verify epoxy kits have been installed on field wiring. <br /> See Veeder Root manual in manager's office for further <br /> information. <br />