Laserfiche WebLink
Facinty: Quik Stop Market #121 <br />Address: 1196 W. Louise Avenue <br />Test Equipment used: AcuRite TM <br />Test Method By: Manufacturer <br />City, state Manteca, CA 96336 <br />Line Manufacturer: Smith <br />Test Date: January 30, 2008 <br />Line Matedal FRP <br />Line # <br />Line Product <br />Line Diameter [Inches] <br />Line Length [Feet] {Est.} <br />Line Capacity [Gallons] (Approx.) <br />Line Pressure @ Dispenser [PSI] <br />Test Pressure [PSI] {1'/i x LP} {Min 50} <br />"STP" Isolation Mechanism <br />"Disp." Isolation Mechanism <br />Time Line Shut Down <br />Test Start Time <br />Test End Time <br />Test Duration [h:mm] <br />Initial Cylinder Level {ICL} <br />Final Cylinder Level {FCL} <br />Volume Lost [Gallons] {ICL - FCL} <br />Indicated Leak Rate [GPH] <br />Pass / Fail Threshold [GPH] <br />TEST RESULT <br />Comments: <br />0 2006 Walton Engineering, Inc. <br />1 <br />Gasoline - 87 <br />2 <br />105 <br />17 <br />27 <br />50 <br />Ball Valve <br />Shear Valve <br />8:36 AM <br />10:20 AM <br />10:50 AM <br />0:30 <br />0.0775 <br />0.0775 <br />0.0000 <br />0.0000 <br />0.0100 <br />PASS. <br />2 <br />Gasoline - 91 <br />2 <br />115 <br />19 <br />28 <br />50 <br />Ball Valve <br />Shear Valve <br />8:36 AM <br />10:20 AM <br />10:50 AM <br />0:30 <br />0.0825 <br />0.0825 <br />0.0000 <br />0.0000 <br />0.0100 <br />PASS <br />