Laserfiche WebLink
WESTERN AMERICA TANK TESTING, INC. <br /> 3131 Fairhaven Drive <br /> Bakersfield, CA 93308 <br /> (805) 322-9827 <br /> ANNUAL 3-STEP RED JACKET LEAK DETECTOR TEST <br /> OWNER QUIK STOP MARKET <br /> LOCATION Ripon, CA. #125 DATE 10/06/90 <br /> PRODUCT: e ulcer Unleaded, Premium Unleaded, Diesel (Circle one) <br /> NOTE: Use separate form for each Tank <br /> ( 1 ) Running Pressure 23 , (2) Shut-Off Pressure -18 <br /> 4 <br /> (3) Amount of Product Released thru Bibcock- to Zero 4 oz . <br /> (4) With Valve Open--Start STP - List Pressure 6 P. S . I. , <br /> (5) Reduce Flow to Rate of 7 oz. per Minute - List Pressure at this Flow <br /> Rate 7 P. S . I . , <br /> (6) Turn STP Off - Let Pressure drop to zero thru Leak just created- - List <br /> time for Gauge to Reach Zero min. 3 sec. , <br /> (7) Turn the STP back on - Keep Leak Rate at Bibcock - List pressure <br /> 8 P. S . I . Flow Rate at Nozzle 1/4 G. P.M. , <br /> (8) Stop Leak with STP still on - Does Leak Detector reset X yes no <br /> If yes - How long to reset min 1 sec. <br /> (9) Turn STP off List. pressure 21 P. S . I . , <br /> (10) Turn STP back on —List time to reach pressure rise min. l sec. - <br /> ( 11) List Pressure 19 P. S . I . , <br /> ( 12) Open Nozzle and List Pressure 23 P. S . I . <br /> SATISFACTORY LEAK DETECTOR X Yes No, <br /> LEAK DETECTOR <br /> Model Red Jacket , Date Code & Serial # <br />