Laserfiche WebLink
RECENED <br /> 0 b ?A <br /> I N-fAL <br /> 5N1jROtqME <br /> 4. TANK ANNULAR TESTING Awa <br /> Test Method Developed By: Tank Manufacturer Industry Standard Professi ngineer <br /> E]Other(Specify) <br /> Test Method Used: []Pressure Vacuum ❑Hydrostatic <br /> E]Other(Specify) <br /> Test Equipment Used:Test plugs,venturi pump and gauges Equipment Resolution: 0.5% inHg <br /> ell <br /> N 7P 1`4 <br /> Tank#87 Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' OYes (D No [-]Yes E]No []Yes [-]No E]Yes E]No <br /> Tank Capacity: 20k <br /> Tank Material: Fiberglass <br /> Tank Manufacturer: Zerxes <br /> Product Stored: Gasoline <br /> Wait time between applying <br /> pressure/vacuum/water and 10 Minutes <br /> starting test: <br /> Test Start Time: 10:15 AM <br /> Initial Reading(Ri): 7 inHg inHg inHg inHg <br /> Test End Time: 11:15 AM <br /> Final Reading(RF): 7 inHg inHg inHg inHg <br /> Test Duration: 1 Hour <br /> Change in Reading(RF-R,): 0 <br /> Pass/Fail Threshold or Criteria: 0 <br /> Test Result: 0 Pass n Fail El Pass El Fail OPass OFail El Pass F-1 Fail <br /> Was sensor removed for testing? ®Yes [-]No [INA [-]Yes EjNo EINA E]Yes E]No [INA E]Yes []No ❑NA <br /> Was sensor properly replaced and RYes [jNo [:INA []Yes []No EINA E]Yes[:]No nNA [:]Yes [:]No ❑NA <br /> verified functional after testina? I <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Tested 87 Tank Per Inspector. <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />