Laserfiche WebLink
PETRO-TECHZ ENVIRONMENTALVICES <br /> Site:United Parcel Service Address: 1532 North Broadway Date of Tests: 6/15/2009 <br /> City/State/Zip: Stockton, CA 95205 <br /> RED JACKET FIELD TEST APPARATUS LINE LEAK DETECTOR TEST DATA SHEET: <br /> Leak Detector#1/ Leak Detector#2/Leak Detector#3/Leak Detector#4 <br /> Product: Diesel ] ) <br /> LD Mod:Vaporless 99LD2000] ] 1 <br /> Serial#: 08101130 ] 1 1 <br /> Drain Back: 25 Ml. J ] <br /> Trip Time: 1.5 Sec. j ] <br /> Test Rate: 189 MI./Min. <br /> F. E. PSI: 31 psi. ] ] ] <br /> Trip PSI• 22 psi. <br /> PASS/FAIL: Pass ] ] <br /> I certify the above tests were conducted on this date according to the eclui meat <br /> manufacturer's procedures and limitations and the results as listed to my lrrrowledge are true <br /> and correct. <br /> Tech. Name:Dan Zeman Tech. (Signature):, -- - <br /> Date:June 15,2009 CA SWRCB Tank Tester,Lic. #1535 CA UST Service Tech.,#5243781-UT <br /> The mecAwicalleak detector test pass/fail is determined using a low}low threshold trip rate <br /> of 189 M1/Min(=3"h)or less 410 psi as set by"Red Lacket Field Test Apparatus Testing <br /> Procedure". <br /> Petro-Techz Environmental Services PO Box 2941 Paradise.CA 95967-2941 Ph:(530)680-2905 Fax:(530)87248648 <br /> PAGE 4OF5 <br />