Laserfiche WebLink
STOCKTON SERVICE STATION EQUIPMENT C . INC. <br /> 808 N. UNION STREET <br /> STOCKTON, CA 95205-4152 <br /> PHONE 209.464.8333 FAX 209.464.8349 <br /> LDT-890 LEAK DETECTOR TEST RECORD <br /> CUSTOMER: United Parcel Service DATE: March 25,2009 <br /> LOCATION: 1532 N.Broadway <br /> CITY: Stockton STATE: CA ZIP: 95205 <br /> TECHNICIAN: Eric Molgaard PRODUCT: DIESEL <br /> Submersible Pump Identification <br /> Manufacturer Model Serial Number <br /> Red Jacket <br /> Leak Detector Identification <br /> Manufacturer Description Other Style Leak Detector <br /> VMI Diaphragm-type <br /> Piston-type Z <br /> Leak Detector in Submersible Pump <br /> Test at Dispenser <br /> 1. Operating Pump Pressure 30 psi (Purging Test System) <br /> 2. Gallons per hour rate 3 (Leak Test,-Phase I) <br /> 3. Line pressure with pump shut off 15 psi (Leak Test Phase I) <br /> 4. Bleed-Back Test with pump off 80 ml (Bleed-back Test) <br /> 5. Step-through time to full flow 4 seconds (Step-through Time) <br /> 6. Leak detector stays in leak search position. (Leak Test Phase II)Yes X No <br /> LEAK DETECTOR TEST <br /> Note: Pass=Leak detector fes test protocol <br /> Fall =Leak detector fails test protocol <br /> Pass X <br /> Fail <br /> Form 890C <br /> Vaporless Manufacturing,Inc. <br /> Prescott Valley,AZ <br />