Laserfiche WebLink
a <br />EPA regulations cover Leak Detection, Corrosion Protection, and Spill/Overfill <br />Prevention. The owner is provided compliance options for new and existiwi� <br />tanks and piping systems. <br />New Tank installations have two options: <br />1. Monthly Tank Testing - OR - <br />2. Monthly Inventory Control and Tank Tightness Testing Every 5 years <br />(This option can only be used for 10 years after installation) <br />Existing Tanks have 3 options: <br />1. Monthly Monitoring <br />2. Monthly Inventory Control andAnnual Tank Tightness Testing <br />(This option can only be used until December 1998) - OR - <br />3. Monthly Inventory Control and Tank Tightness Testing Every 5 Years <br />(This option can only be used for 10 years after adding corrosion protection <br />and spill /overfill prevention or until December 1998, whichever date is <br />later) <br />New and Existing Pressurized Piping must provide one of the options from each <br />set: <br />1. Hourly Test Consisting of : Automatic now Restrictor - OR - Automati(4- <br />Shutoff Device - OR - Continuous Alarm System. - AND - <br />2. Annual Line Test - OR - Monthly Line Test <br />Spill/ Overfill Prevention for all Tanks <br />1. Catchment Basins - AND - <br />K. Automatic Shutoff Devices - OR - Overfill Alarms - OR - Ball Flom <br />Valves. <br />Corrosion Protection is not discussed in this presentation. <br />Control Engineers, U.S.A. Page 3 <br />