Laserfiche WebLink
Stiril Diameter: <br />42" <br />4,Z.. <br />1+4 <br />Sump 1De tlr. <br />71,E <br />72" <br />67" <br />Height from Wank Top to Top of <br />21" <br />23" <br />19" <br />Hi best 1'i in � Penetration: <br />10:00 <br />initial Reading(R i <br />Height from "lank Top to Lowest <br />" <br />49" <br />Sol, <br />Electrical Penetration: <br />8:50 <br />9:40 <br />10:30 <br />Condition of sump prior to <br />Dry <br />Dry <br />Dry <br />testin : <br />Test Duration: <br />30 Minutes <br />Portion of Sump Tested <br />Water Level 23' <br />Water Level 25" <br />Water Level 2 <br />Wait time between applying <br />5 Minutes <br />5 Minutes <br />5 Minutes <br />water and startin r test: <br />"Gest Start Time: <br />_ <br />� 8:20 <br />:10 <br />10:00 <br />initial Reading(R i <br />.001 <br />,001 <br />.001 <br />'rest End Time: <br />8:50 <br />9:40 <br />10:30 <br />%incladin <br />.001 <br />,001 <br />001 <br />Test Duration: <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />khan e in eadin r~ i)% <br />0 <br />0 <br />0 <br />Pass/hail Threshold or Criteria: <br />M5/30Minutes <br />005/ 0Minutes <br />.00 i30Minutes <br />Test aft. <br />Pass <br />Vass <br />Pass <br />is there a sensor in the suin ? <br />Yes <br />Yes <br />Yes <br />Does the sensor alarm when <br />either product or water is <br />Yes <br />Yes <br />Y+ <br />detected? <br />Was sensor removed for testing? <br />"Yes <br />Yes <br />Yes <br />Was sensor properly replaced and <br />Yes <br />Yes <br />Yes <br />verified functional after testing? <br />