3 <br />0 <br />FPR il '97 15'26 <br />11 <br />AT&T <br />Communications <br />ATST <br />J110 ff. TURN.SR ROAD <br />LODX, CAI,-TFmm-rA <br />OVERFILL PR07'ZC2'XOS SYSTEM -- MANUAL NI RING <br />Prior to delivery of fuelt a visual mnitoring of th& liquir <br />'I level <br />of "0 tank will be Pe-rfOxzwd Which tvill Include 'noting the amount <br />of gallons and percent'fill UsIng the djq�jtal display guage locatea <br />near the central monitorinq panel. In addition, the fill level <br />of the tank will be goasured usin4 a dip stick-tO calculate the <br />amount of gallons in the 'tank. Both resdin!75 Will be compared to <br />daterniine amount of product required, <br />2. The tank will'have an avai2ab2e capacity of lo3v'of tjW load to <br />be dropped, or the total'10ad plus 200 gallon capacity whichaver <br />is less, 'as determined by storage tank v1sua2 monitoring. in <br />addition, char�s ars l0catcd in the eymzgency power room wMcl) <br />indicate how much product can be delivered safely Into the tank <br />based an the liguld lOve2 measuzOd bY the dip stick. <br />J. Metered xnput -- jr, the load to be dellvexed is,2000 "lic -5 or It - <br />it will be run through a Imter as It is being dtopped int . o <br />undergrounc? stgriqe tank. In addition the dlqdta� fuel guaqe will <br />be monitored, Xf th& 10ad Is more than 2000 gallons, it shall be <br />m0nitoxed Off5ite at a batch plint. The product shall rull thrguyl, <br />a Mter when loaded Into the truck. <br />0 <br />