Laserfiche WebLink
IN—TANK SETUP <br /> T 1 :DIESEL TK#CAK482U001 <br /> PRODUCT CODE 3 LEAK TEST METHOD <br /> _ _ <br /> THERMAL COEFF : .000450 <br /> RS-232 END OF MESSAGE TANK DIAMETER : 107.00 TEST DAILY : ALL TANK <br /> DISABLED TANK PROFILE . 1 PT <br /> FULL VOL : 15000 START TIME : 12:00 AM <br /> AUTO DIAL ALARM SETUP TEST RATE :0.20 GAL/HR <br /> FLOAT SIZE: 4.0 IN. DURATION : 24 HOURS <br /> D 1 :C:RLL CENTER <br /> WATER WARNING 15 TST EARLY STOP:DISABLED <br /> IN—TANK ALARMS HIGH WATER LIMIT: 2.0 LEAK TEST REPORT FORMAT <br /> ALL:LEAK ALARM <br /> ALL:HIGH WATER ALARM MAX OR LABEL VOL: 15000 NORMAL <br /> � <br /> ALL:SUDDEN LOSS ALARM OVERFILL LIMIT 90% <br /> ALL:PERIODIC TEST FAIL 1350 <br /> HIGH PRODUCT 95 <br /> LIQUID SENSOR ALMS 14250 ° <br /> ALL:FUEL ALARM DELIVERY LIMIT 10% <br /> ALL:HIGH LIQUID ALARM 1500 <br /> ALL:LOW LIQUID ALARM LOW PRODUCT 500 <br /> RLL:LIQUID WARNING LEAK ALARM LIMIT: 99 <br /> D 2:EMCC SUDDEN LOSS LIMIT: 99 <br /> TANK TILT 0.00 LIQUID SENSOR SETUP <br /> IN—TANK ALARMS PROBE OFFSET 0.00 — — — <br /> ALL:LEAK ALARM — — — — — — — — — <br /> ALL:HIGH WATER ALARM SIPHON MRNIFOLDED TANKS L 1 :SOUTH SUMP <br /> ALL:SUDDEN LOSS ALARM T#: NONE TRI—STATE (SINGLE FLOAT) <br /> ALL:PERIODIC TEST FAIL LINE MANIFOLDED TANKS CATEGORY : PIPING SUMP <br /> LIQUID SENSOR ALMS T#: NONE <br /> ALL:FUEL ALARM L 2:ANNULAR <br /> ALL:HIGH LIQUID ALARM TRI—STATE (SINGLE FLOAT) <br /> ALL:LOW LIQUID ALARM LEAK MIN PERIODIC: 0 CATEGORY : ANNULAR SPACE <br /> ALL:LIQUID WARNING 0 <br /> LEAK MIN ANNUAL : 0% <br /> 0 L 3:NORTH SUMP <br /> TRI—STATE (SINGLE FLOAT) <br /> a PERIODIC. TEST TYPE CATEGORY PIPING SUMP <br /> STANDARD <br /> ANNUAL TEST FAIL L 4:GEN ROOM TRENCH <br /> ALARM DISABLED TRI—STATE (SINGLE FLOAT) <br /> CATEGORY : OTHER SENSORS <br /> PERIODIC TEST FAIL <br /> ALARM DISABLED <br /> GROSS TEST FAIL <br /> ALARM DISABLED <br /> ANN TEST AVERAGING: - OFF <br /> PER TEST AVERAGING: OFF <br /> TANK TEST NOTIFY: OFF <br /> TNK TST SIPHON BREAKOFF <br /> DELIVERY DELAY 1 MIN <br /> PUMP THRESHOLD : 10.00° <br /> TEST DATE: 06/23/2008 CLIENT: ATT, GEOPAR: CAK482 PAGE OF <br />