r <br />1 <br />WARNING: All internal piping must be at least 4" [6" for 12' diame- <br />ter tanks) from the tank bottom. <br />CAUTION: All single wall and double wall tanks must be vented to <br />atmospheric pressure. <br />Refer to Figure 10-1 and Table 10-1 to determine the correct dimen- <br />sions to size internal pumps and piping. <br />When the tank's interstitial space is filled with a liquid, the space <br />must be vented. It is sufficient to drill a 1/4" - diameter hole in the <br />side or cap of the riser pipe as supplied by the installer. When the <br />groundwater level will be high enough to enter a drilled vent hole, <br />install a vent line from the riser pipe to above grade level. <br />When the interstitial space is dry. it is not necessary to vent the <br />space to atmosphere. <br />It is the installer's responsibility to select a thread sealant that is <br />compatible with the product being stored. Some sealants cannot <br />be used with some products. If necessary, remove, clean and <br />redope all plugs. <br />B B E H <br />\� .�.A B D -G <br />Dir'EN'51ON :.INE DETAIL DIMENSION LINE DETAIL <br />SINGLE WALL B DOUBLE WALL :'I DOUBLE WALL I <br />SCALE: 1/16 SCALE: 1/16 <br />...,G..E WALE_ DOUBLE WALL 11 DOUBLE WALL 1 <br />RIBBED OUTER WALL SMOOTH OUTER WALL <br />NOTE. <br />ALL FITTING DIMENSIONS ARE MEASURED FROM THE TOP OF A <br />SERVICE FITTING TO THE INSIDE BOTTOM OF THE TANK AND <br />INCLUDE GAUGE PLATE CLEARANCE. <br />2 _ ,NTERIOP DIAMETERS DO NOT INCLUDE GAUGE PLATE CLEARANCE <br />INTERIOR DIMENSIONS (IN) <br />TANK <br />DIA. .A.. B . „D,. „D„ i ::E„ 'T' „G, .,H„ :,I„ <br />511 34.50 48.00 151.50 156.625 48.00 <br />1 _ 11 < 0, 78.00 71.36 72 5 1, 77715 0.625 125 8 25 1 71.36 <br />-- -188 251---1100.50 91.188 <br />- 91.188 9215 �- _—� <br />5 �u 58.00 0 <br />0 !2100 126 00 119.16 120,75 125 75 ! 118 50 123,50 128.6251 11916 <br />2 138.25 143 25 <br />All piping must conform to all applicable codes and standards. See <br />INTRODUCTION. <br />WARNING: When pressure testing the piping, the tank must be <br />isolated from the piping system. The test pressures for piping <br />may cause the tank to explode and cause death, severe personal <br />injury or property damage. <br />CAUTION: When extending monitoring or vapor recovery piping to <br />the surface, be sure that the at -grade fittings are different from any <br />fill fittings and will not accept standard fill hoses. <br />E <br />3C <br />If the tank has a sump or a bottom fitting, take extra care that the <br />tank does not rest or roll on it prior to installation. <br />During installation, provide a clear area in the backfill bedding, so <br />that the tank rests on the backfill bedding and the sump or bottom <br />fitting is clear. After setting the tank, fill and tamp the resulting void <br />by hand before continuing the backfilling. <br />1ACKFILLING+TO GRAC <br />When the tank has been set, tested and backfilled, and all piping <br />and venting has been completed, the balance of the backfill material <br />may be added <br />When the tank has been backfilled to subgraue- take the !11181 <br />diameter reading (Deflection reading "B" on the clheckiisr <br />The same material as specified in Section 3 must be used to <br />completely fill excavation. The backfill must be free of debris. Any <br />blocks or bricks used as support material during piping must be <br />removed prior to completion of backfilling. Safety measures. such <br />as placing barricades until installation is complete, should be usec <br />around the excavation site. <br />Be sure that the installation meets all of the requirements of <br />minimum cover as specified in Section 4. <br />Be sure that the checklist is properly completed <br />DIPSTICK PREPARATION <br />Drive a small -headed, non -sparking (e.g, brass) nail halfway into a <br />wooden dipstick 1" above its base. <br />FIRST DIAMETER READING (PRIOR TO BACKFILL) <br />1. Place the dipstick into a service fitting. <br />2. Measure and record the distance from the tank bottom to the <br />top of the fitting. <br />3. Pull the dipstick up until the exposed nail catches on the inside <br />top of the tank. <br />4. Measure the distance from the tank top (inside) to the top <br />of the fitting. Subtract 1 " from this measurement and record <br />the distance. <br />5. Subtract the second distance from the first and record this <br />value as reading 'A' on the Installation Checklist. <br />SECOND DIAMETER READING (AFTER BACKFILL) <br />1. Place the dipstick into a service fitting with a standpipe <br />installed to subgrade. <br />2. Measure and record the distance from the tank bottom to the <br />top of the standpipe. <br />3. Pull the dipstick up until the nail catches on the inside top of <br />the tank. <br />4. Measure the distance from the tank top (inside) to the top of <br />the standpipe. Subtract 1" from this measurement and record <br />the distance. <br />5. Subtract the second distance from the first and record this <br />value as reading "B" on the Installation Checklist. <br />