Laserfiche WebLink
EQUIPMENT USED AT THIS FACILITY: -Ronan System X76 ETM The equipment detects a leak rate of 0.2 gallons per <br />hour during the four hour test. <br />FACILITY ADDRESS: 880 Victor Road Lodi CA 95240 <br />DAILY VISUAL OBSERVATION: On a daily basis the dealer or his designate will perforin the inventory readout which <br />will indicate that the sensor and the monitor control panel are working. <br />MONTHLY TEST: Each tank will be tested monthly following the procedure listed on the attached <br />ANNUAL CERTIFICATION: The dealer will certify annually to the local agency listed below that he has performed all <br />monthly casts and no leaks were indicated. <br />Local Agency Name: County of San Joaouin O.E.S. <br />Local Agency Address: 222 East Weber Ave„ Stockton <br />Local Agency Phone: 209-468-3962 <br />FAILED LEAK TEST: In the event of a failed leak test, the dealer will perform the steps outlined on the attached sheet <br />entitled: 'Monthly Test Procedures" Station personnel will also: <br />1. Notify the Responsible Personridl: <br />Primary Contact: Name:_Jr2nald Swim Title: Dealer <br />Address: P.O. Box 460. Burson, Ca <br />Bus #/Home #: 299-368-3755 1209-763-5369 <br />Secondary Contact: Name:_Bud Swim Tide: Manager <br />Address: 9458 Sara Street Elk Grove Ca <br />Bus #/Home #. 209-368-3755 / 916-686-5872 <br />2. Notify the Shell Maintenance Desk: 510-675-6154. <br />3. Recast your tanks. <br />YOU MUST RECEIVE A PASS TEST RESULT EVERY MONTH FOR EVERY PRODUCT AND KEEP TEST <br />RESULTS IN YOUR GREEN BOOK. IF YOU DO NOT RECEIVE. A PASS, YOU MUST NOTIFY THE SHELL <br />MAINTENANCE DESK AT 510-675-6154. <br />MONTHLY TESTING PROCEDURES <br />1. Monthly, the system is programmed to perform a leak detection test. Each product tank will be tested separately. <br />2. Each tank will not have received a fuel drop not less than 4 hours before the test begins. (i.e. if the test starts at 12:01 <br />A.M., then you must not receive a fuel delivery after 8:00 P.M. for the product being tested that evening.) <br />3. During testing, there will be no inputs or withdrawals from the tank. Pumping product during a test will invalidate <br />the test. (Tests run from 12:01. A.M. to 5:00 A.M.) Tanks are initially probranuned to test as follows: <br />Regular - Morning of the 2nd <br />Plus - Morning of the 3rd <br />Premium - Morning of the 4th <br />Diesel - Morning of the 5th <br />