Multiple tank in:atallation will also ire a <br />minimum of 12 inchos between tank measured from <br />each outside edge. <br />ANCHORING <br />7.0 Certain situations require the use of properly <br />designed anchor straps to overcome existing <br />buoyant forces. The straps are used in conjunction <br />with a concrete holddown slab or deadman <br />anchors. <br />CAUTION: Use of steel cable or round <br />bar is prohibited. <br />INE USE Of SYM <br />CABLE ANO ROUND BAA <br />AS Nolo 00W14 STRAPS <br />IS PROHIBiTtO <br />7.1 A pad of inert, isolation dielectric material must <br />be used to separate the steel anchor strap from the <br />tank. Isolation pads are not required when the holddown <br />strap material is approved fiberglass or polyester webbing. <br />BACKFILL <br />8.0 Only the following approved backfill material may <br />be used. <br />1. Clean washed sand. <br />2. Pea Gravel - (particle size must be not less than <br />1/8 inch or more than 314 inch) <br />3. Washed stone or gravel crashinge - <br />(angular particle size required to be not less <br />than 1/8 inch or more than 1/2 inch) <br />8.1 Special care should be used to ensure that the <br />backfill is properly installed to evenly support the <br />bottom quadrant of the tank. <br />NOTE: Do not backfill in layers using different <br />materials. <br />8.2 If tank must 011asted during the backfill <br />procedure, at no time may the liquid exceed the <br />height of the compacted backfill surrounding the <br />tank. <br />8.3 The tank shall be encompassed by the proper <br />backfill and extending to a minimum of 12 inches <br />over the top of the tank. <br />8.4 Areas subject to heavy vehicular traffic shall have <br />a protective cover of 18 inches clean, compacted <br />soil with either 6 inches of reinforced concrete or 8 <br />inches of asphalt paving. If compacted soil is the . <br />only cover, it shall be a minimum of 36 inches <br />deep. <br />8.5 Areas not subject to heavy vehicular traffic shall <br />have a proteetiv2 cover of a minimum I8 inches of <br />clean compacted soil covered by 4 inches of <br />reinforced concrete or 6 inches of asphalt paving. If <br />compacted soil is the only cover, it shall be a <br />minimum of 24 inches deep. <br />8.6 Finishing Instructions; A faberglassing kit is <br />shipped with tank and provides materials to cover <br />unused openings and external attachments, such <br />as lifting lugs. All finishing work will be done <br />prior to backfilling. <br />9.0 For Glasteel II warranty to be initiated, the <br />Installation Checklist must be properly filled out <br />by the customer, and returned to the Modena <br />Welding Co. subsidiary from which the tank was <br />fabricated. The Installation Checklist must be <br />returned within 30 days after date of installation. If the <br />Glasteel II tank has not been installed within 90 days' of <br />delivery from the manufacturer. it is required that the tank be <br />re -certified by the manufacturer, at the owner's expense, prior <br />to installation. , <br />10.0 Maintenance of Underground Storage Tanks <br />The primary tank should be inspected monthly for the <br />presence of water. Inspections should take place at the <br />lowest possible points inside the primary tank. Remove <br />any water found. Water and sediment in fuel can cause <br />plugging of filters. Also, bacterial growth originating from <br />the fuel, can cause filters to plug and corrosion of tanks <br />and lines. A report by the US Department of Energy, <br />BNL 48406, provides information on methods to test for <br />and remove water, test for bacterial presence in fuel, tank <br />cleaning and fuel additives. Failure to remove water from <br />the tank may void your warranty. <br />•WMIZENMA <br />Corporate Office (270) 6"400 <br />Modern Welding Company of Owensboro, Inc (270) 683-5323 <br />Modern Welding Company of Ohio, Inc (740) 344-9426 <br />Modern Welding Company of Florida, Inc (407) 843-1270 <br />Modern Welding Company of Texas, Inc (713) 675.4211 <br />Modem Welding Company of Texas, Inc (817) 636.2216 <br />Modern Welding Company of Iowa, Inc (319) 754.6677 <br />Modern Welding Company of California, Inc (559) 275.9353 <br />Modern Welding Company of Georgia, Inc (706) 722.3411 <br />FORM Glas2k%, ®1-2001 MWCO <br />