Laserfiche WebLink
1k Me <br />TEST DATE: 05/30/01 <br />CLIENT:EQUIVA SERVICES, LLC <br />Tank ID: 2 <br />Product: REG UNLEAD <br />Capacity in gallons: 14,976 <br />Diameter in inches: 114.00 <br />Length in inches: 342 <br />Material: DW FIBERG <br />COMMENTS <br />Dipped Water Level: <br />Dipped Product Level: <br />Probe Water Level: <br />Ingress Detected: Water <br />Test time: <br />Inclinometer reading: <br />VacuTect Test Type: <br />VacuTect Probe Entry Point: <br />Pressure Set Point: <br />Tank water level in inches: <br />Water table depth in inches: <br />Determined by (method): <br />Result: <br />I COMMENTS <br />COMMENTS <br />L TANK INFORMATION ANI <br />lip rankmWbW <br />8900 SHOAL CREEK, BUILDING 200 <br />AUSTIN, TEXAS 78757 (512) 451-6334 <br />Tank manifolded: No <br />Vent manifolded: NO <br />Vapor recovery manifolded: yES <br />Overfill protection: yEs <br />Overspill protection: yEs <br />Installed: ATG <br />CP installed on: / / <br />Make: <br />Bubble Ullage Model: <br />S/N: <br />Open time in sec: <br />Holding psi: <br />NOT Resiliency cc: <br />TESTED Test leak rate ml/m: <br />Metering psi: <br />Calib. leak in gph: <br />Results: <br />Material: DW FIBERG <br />Diameter (in): <br />2.0 <br />Length (ft): <br />100.0 <br />Test psi: <br />45 <br />Bleedback cc: <br />0 <br />Test time (min): <br />60 <br />Start time: <br />09:50 <br />End time: <br />10:50 <br />Final gph: <br />0.000 <br />Result: <br />PASS <br />Pump type: <br />PRESSURE <br />Pump make: <br />FE PETRO <br />COMMENTS <br />EST RESULTS <br />WORK ORDER NUMBER2216947 <br />SITE:SHELL 204-4416-0806 <br />Bottom to top fill in inches: <br />180.0 <br />Bottom to grade in inches: <br />188.0 <br />Fill pipe length in inches: <br />66.0 <br />Fill pipe diameter in inches: <br />4.0 <br />Stage I vapor recovery: <br />DUAL <br />Stage II vapor recovery: <br />ASSIST <br />New/passed Failed/replaced New/passed Failed/replaced <br />L.D. #1 L.D. #1 L.D. #2 L.D. #2 <br />NOT <br />TESTED <br />NOT <br />TESTED <br />NOT NOT NOT <br />TESTED TESTED TESTED <br />Impact Valves Operational: Uffl<NONN <br />Printed 06/04/2001 09:31 <br />