0 <br /> PREVENTATIVE MAINTENANCE <br /> Annually, inspect the flapper in the 71 SO to see that it is open by looking down the drop tube opening. Test the <br /> 71 SO drop tube seals with CARB procedure TP-201.1 D. If the drop tube seal passes testing, no further <br /> maintenance is required. If the drop tube fails testing, replace the drop tube seal with OPW P/N: H11931 M for 4" <br /> Tubes. Re-test the 71 SO drop tube with CARB procedure TP-201.1 D. The lower tube o-ring seal OPW P/N: <br /> H 14840M can also be replaced. If this does not correct the leak the 71 SO needs to be replaced. <br /> CAUTION: Do not insert any foreign object into drop tube if flapper is in the closed position. For example <br /> a tank level measuring stick. This will damage the valve and void the Warranty. ALWAYS check flapper <br /> location before"sticking"the tank. If flapper is in the closed position the tank is either over filled and you <br /> need to wait until the liquid level goes down or the 71 SO is damaged and needs to be replaced. <br /> 71 SO Performance Specifications: <br /> This Overfill Prevention Valve has been manufactured and tested to, and met, the following California <br /> specifications. Performance Requirement: Leak rate to be less than or equal to 0.17 CFH @ 2.0"W.C. <br /> Torque Specification: <br /> Taptite Screws,#10-24 thread cutting, 20 in-lbs minimum to 35 in-lbs maximum. <br /> Important: Leave these installation instructions and maintenance procedures with the station <br /> operator. <br /> Notice: OPW products must be used in compliance with applicable federal,state,and local laws and regulations. Product <br /> selection should be based on physical specifications and limitations and compatibility with the environment and material to be <br /> handled. All illustrations and specifications in this literature are based on the latest production information available at the time <br /> of publication. Prices, materials,and specification are subject to change at any time,and models may be discontinued at any <br /> time, in either case,without notice or obligation. <br /> Standard Product Warranty <br /> OPW warrants that products sold by it are free from defects in materials and workmanship for a period of one year from the <br /> date of manufacture by OPW(ECO products two years from date of manufacture.)Proof of purchase may be required. As the <br /> exclusive remedy under this limited warranty, OPW,will at its sole discretion, repair, replace,or issue credit for future orders <br /> for any product that may prove defective within the one year date of manufacture period(repairs, replacements,or credits may <br /> be subject to prorated warranty for remainder of the original warranty period,complete proper warranty claim documentation <br /> required.) This warranty shall not apply to any product that has been altered in any way,which has been repaired by any party <br /> other than a service representative authorized by OPW,or when failure is due to misuse,or improper installation or <br /> maintenance. OPW shall have no liability whatsoever for special,incidental or consequential damages to any party,and shall <br /> have no liability for the cost of labor,freight,excavation,clean up,downtime, removal, reinstallation,loss of profit,or any other <br /> cost or charges. <br /> For any product certified to California 2001 standards,OPW warrants that product sold by it are free from defects in <br /> material and workmanship for a period of one year from date of manufacture or one year from date of registration of <br /> installation not to exceed 15 months from date of manufacture by OPW. <br /> THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED,AND SPECIFICALLY THE <br /> WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. THERE ARE NO WARRANTIES, <br /> WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. <br /> O P V1✓- <br /> A PDOVER r COMPANY <br /> P.O. Box 405003"Cincinnati, Ohio 45240-5002 <br /> 1-800-422-2525 Domestically <br /> 513-870-3315 Internationally <br /> www.opw-fc.com <br /> Copyright, 2007-OPW Fueling Components Inc., Cincinnati, OH <br /> Printed in U.S.A. p/n H15524PA—Rev. E 6/07 <br /> OPW 71 SO Overfill Prevention Valve Page 12 <br />