Laserfiche WebLink
SWRCB,January 2002 Page 2- <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes: <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested: El <br /> Test Method Developed By: ❑ Spill Bucket Manufacturer F—xl Industry Standard ❑ Professional Engineer <br /> 0 Other(Spec) <br /> Test Method Used: ❑ Pressure Fx-1 Vacuum F-1 Hydrostatic <br /> Other(Specify) <br /> Test Equipment Used: Equipment Resolution: <br /> Spill Box# 87-1 1 Spill Box# 87-2 2 Spill Box# 91 3 Spill Box# <br /> Bucket Diameter: 13 13 13 <br /> Bucket Depth: 15 15 15 <br /> Wait time between applying <br /> pressure/vacuum/water and 1 MIN 1 MIN 1 MIN <br /> starting test: <br /> Test Start Time: 1250 1244 1241 <br /> Initial Reading(Ri ): -30 -30 -30 <br /> Test End Time: 1251 1245 1242 <br /> Final Reading(RF ): -30 -30 -30 <br /> Test Duration: 1 MIN 1 MIN 1 MIN <br /> Change in Reading(R F-14 0 0 0 <br /> Pass/Fail Threshold or 4 4 4 <br /> Criteria: <br /> ifflIMEMEMEMEMM;�ii!ii!iiii!i!!�!lliim ! !!!i i I i i I 1 11 I! I I i i I !!I I I <br /> Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />