Laserfiche WebLink
Page 1 of 1 <br /> SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Fill Riser Containment Sumps l <br /> Fill Riser Containment Sumps are Present, but were Not Tested <br /> Test Method Developed By: r Spill Bucket Manufacturers Industry Standard r Professional Engineer <br /> r Other (Specify): <br /> Test Method Used By: r" Pressure r^ vacuum r# Hydrostatic <br /> r4 Other (Specify): <br /> Test Equipment Used: LAKE TEST Equipment Resolution: 0.0625 in. <br /> Split Box'# Spill Box # Spill Box #' <br /> Tank supreme SUPREME Tank regular I REGULAR Tank regular 2 REGULAR Spill Box # <br /> Fill- Direct Fill - Direct Fill'- Direct <br /> Bucket Diameter: 12.00 12.00 12.00 <br /> Bucket Depth: 13.75 10.75 13.50 <br /> Wait time between applying <br /> pressure/vacuum/water and 5 min 5 min 5 min m i n <br /> starting test <br /> Test Start Time: 09:56:00 09:56:00 09:56:00 <br /> Initial Reading 13.75 in. 10.75 in. 13.50 in. <br /> Test End Time: 10:56:00 10:56:00 10:56:00 <br /> Final Reading p,,: 13.75 in. 10.75 in. 13,50 in. <br /> Test Duration: 1 hr 1 hr 1 hr <br /> Change in Reading m,,�,: 0.00 in. 0.00 in. 0.00 in. <br /> Pass/Fail Threshold or Criteria: +/- 0.00 +/- 0.00 +/- 0.00 <br /> Fest Result. Pass- Pass:- - Pass <br /> Comments? (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> I <br /> ( I <br /> I <br /> E 1 <br /> i <br /> I � <br /> 4 <br /> I E, <br /> i f <br /> i I <br /> i 1 <br /> i f <br /> i <br /> f <br /> I <br /> i <br /> W0: 2301260 <br />