Laserfiche WebLink
Integrity an .,+r Systes, <br />,Mr. John Pinasco <br />Pinasco Plumbing & Heating <br />P. 0. Box 55287 <br />Stockton, California 95205 <br />Dear Z1r. Pinasco: <br />TEST DATA AND <br />TEST RESULTS <br />September 29, 1988 <br />Site: Certified Grocers Co. <br />1990 Picoli <br />Following is a summary of the precision testing we recently <br />conducted on your underground storage tank(s). <br />Enclosed are copies of the test worksheets and graphs gene- <br />rated for your submittal to the appropriate governmental agency. <br />A tank system is considered tight, according to the current <br />rules, if the gain is less than .02 or the loss is less than .05 <br />gallons per one hour of testing. If the results are beyond these <br />parameters, you should consider taking some remedial action. <br />TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br />LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br />North 20,000 Diesel -.00551 Yes <br />Please contact us if you need additional assistance or <br />information. <br />Sincerely, <br />c <br />rank Kes r <br />Certified ester <br />800 262-8378 166 Frank West Circle Stockton, CA 05206 (209) 466-8-036- <br />