Page 4 of 6 <br />6. PIPING SUMP TESTING <br />Test Method Developed By: ❑ Sump Manufacturer X ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum X Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: INCON TS -STS V2.1 <br />Equipment Resolution: 0.0000" <br />Sump #STP North Sump #STP South <br />Sump Diameter: 42" <br />42" <br />Sump Depth: 52" <br />49" <br />Sump Material: fiberglass <br />fiberglass <br />Height from Tank Top to Top of 14" <br />14" <br />Highest Piping Penetration: <br />Height from Tank Top to Lowest 20" <br />19" <br />Electrical Penetration: <br />Condition of sump prior to testing: Clean <br />Clean <br />Portion of Sump Tested' 2" Above Highest <br />2" Above Highest <br />Piping Penetration <br />Piping Penetration <br />Does turbine shut down when <br />sump sensor detects liquid (both X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />product and water)?' <br />Turbine shutdown response time 2 Seconds <br />2 Seconds <br />Is system programmed for fail-safe <br />X Yes ❑ No ❑ NA <br />shutdown?' <br />X Yes ❑ No ❑ NA <br />Was fail-safe verified to be <br />X Yes ❑ No ❑ NA <br />operational?* <br />X Yes ❑ No ❑ NA <br />Wait time between applying <br />pressure/vacuum/water and starting 15 Minutes <br />15 Minutes <br />test: <br />Test Start Time: 8:44 / 9:00 <br />9:34 / 9:50 <br />Initial Reading (RI): 4.826 /4.825 <br />3.932 / 3.931 <br />Test End Time: 8:59 / 9:15 <br />9:49 / 10:05 <br />Final Reading (RF): 4.825 / 4.825 <br />3.931 / 3.931 <br />Test Duration: 15 min. each <br />15 min. each <br />Change in Reading (RF -RI): .001/0 <br />.001/0 <br />Pass/Fail Threshold or Criteria: 0.0020" <br />0.0020" <br />Test Result: X Pass D Fail <br />X Pass D Fail <br />Was sensor removed for testing? X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />X Yes ❑ No ❑ NA <br />verified functional after testin ? <br />X Yes ❑ No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />' If the entire depth of the sump is not tested, specify how much was tested. If the answer to M of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG -160) <br />