Laserfiche WebLink
• <br />Page of <br />4. SPILL/OVERFILL CONTAINMENT BOXES <br />Test Method Developed By: ❑ UDC Manufacturer X Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Uses: ❑ Pressure ❑ Vacuum X Hydrostatic <br />❑ Other (Specify) <br />Measuring Equipment Used for Testing: INCON TS -STS V2.1 <br />Spill Box # D1 Fill Spill Box # Spill Box # <br />Bucket Diameter: 20" <br />Bucket Depth: 16" <br />Wait time between applying <br />pressure/vacuum/water and 15 Min. <br />starting test: <br />Test Start Time: 11:15 <br />Initial Reading (RO: 4.879 <br />Test End Time: 11:30 <br />Final Reading (RF): 4.868 <br />Test Duration: 15 Min. <br />Change in Reading (RF -RI): .11 <br />Pass/Fail Threshold: .002 <br />Test Result: Fail <br />Comments — (include information on repairs made to facilitate a passing test and indicate whether a <br />permit was obtained for the repairs) <br />All Hydrostatic test performed twice to insure testing results <br />IM n T T C' T nn11 4 T,.«..,,«.. '1AA A <br />