Laserfiche WebLink
RECEIVED <br /> TAIT DEC12 201 <br /> HEALTH <br /> WLEAK DETECTOR <br /> TESTING <br /> » ti <br /> 6 <br /> Facility Name : Unified Grocers,Inc. Test Date: 11/18/2014 <br /> Location <br /> Tested: 1990 Piccoli Road Technician : Victor Guerrero <br /> Stockton <br /> Cal iforni a <br /> 8017001-UT <br /> 95215 ICC#: <br /> Test I nformation <br /> Product Diesel <br /> Manufacturer FE-Petro <br /> Model STP-MLD-D <br /> New Leak Detector(Yes/No) No <br /> Serial Number MH1393 <br /> Electronic LD(Yes/No) No <br /> Calibrated Test Leak Rate: (189 Yes <br /> mil/min @ 10 PSI)(Yes/No) <br /> Check Valve Holding PSI Yes <br /> Resiliency (Bleed Back MIL) 115 MIL <br /> Slow Flow Metering PSI/(N/A) 10 PSI <br /> Turbine Shut Down Electronic LD NA <br /> (Yes/No/NA) <br /> Slow Flow At Nozzle Yes <br /> (Yes/No/NA) <br /> Opening Time(Seconds) 3 SEC. <br /> Pass/Fail Pass <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility according to the <br /> equipment manufacturers procedures and limitations and the results as listed are to my knowledge true and correct.The <br /> leak detector test pass/fail is determined using a low flow threshold trip rate of 3 gph at 10 PSI. <br /> Technician Signature: Date : 11/18/2014 <br />