Laserfiche WebLink
E YO'Rw®6Mb4k,R4edF <br /> TAIT <br /> LEAK DETECTOR TESTING <br /> Facility Name : Unified Grocers,Inc. Test Date: 11/25/2013 <br /> Location <br /> Tested: 1990 Piccoli Road Technician : Victor Guerrero <br /> Stockton <br /> Cal iforni a <br /> 8017001-UT <br /> 3 95215 ICC#: <br /> Test i nformation <br /> Product Diesel <br /> Manufacturer FE-PETRO <br /> Model STP-MLD-D <br /> New Leak Detector(Yes/No) No <br /> Serial Number MH1393 <br /> Electronic LD(Yes/No) No <br /> i <br /> Calibrated Test Leak Rate: (189 Yes <br /> mil/min @ 10 PSI)(Yes/No) <br /> 3 <br /> Check Valve Holding PSI Yes <br /> Resiliency(Bleed Back MIL) 110.000 <br /> Slow Flow Metering PSI/(N/A) 12 PSI <br /> i <br /> Turbine Shut Down Electronic LD NA <br /> (Yes/No/NA) <br /> 3, <br /> Slow Flow At Nozzle Yes <br /> f <br /> (Yes/No/NA) <br /> Opening Time(Seconds) 7 Seconds <br /> E <br /> Pass/Fail Pass <br /> F <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility according to the <br /> equipment manufacturers procedures and limitations and the results as listed are to my knowledge true and correct.The <br /> leak detector test pass/fail is determined using a low flow threshold trip rate of 3 gph at 10 PSI. <br /> I <br /> JO <br /> Technician Signature: Date ; 11/25/2013 <br /> i <br /> i <br /> .... ., . w. _ _ m_ „ __ ,� ._ __------ - ....... __ ....... _ � . .........�-- . n� <br />