Laserfiche WebLink
�II TAIT <br />LEAK DETECTOR TESTING <br />rl�7 �—' 7�"— <br />ENVIRONMENTALMEMMM <br />LT vl,,, s, <br />DEPARTMENT <br />p. 714; 56018222 www_lalt.cam <br />Test Date: 11/08/2017 <br />Facility ID: 01 Client Name: Unified Grocers, Inc <br />Street Address: 1990 Piccoli Rd. Technician: Garrett Warren <br />City: Stockton ICC #: 8185019 <br />Zip Code / State: 95215 / CA Manufacturer Cert #: <br />Test Information <br />Product <br />Diesel <br />Diesel <br />Manufacturer <br />FE -Petro <br />Vaporless <br />Model <br />STP -MLD -D <br />LD 3000 <br />New Leak Detector <br />Yes/No <br />No <br />No <br />Serial Number <br />00310065 <br />Electronic LD <br />Yes/No <br />No <br />No <br />Calibrated Test Leak <br />Rate: (189 mil/min <br />Yes <br />Yes <br />10 PSI) (Yes/No <br />Check Valve Holding <br />PSI <br />33psi <br />38psi <br />Resiliency <br />(Bleed Back MIL) <br />125ML <br />250ML <br />Slow Flow <br />MeteringPSI /(N/A)8psi <br />16psi <br />Turbine Shut Down <br />Electronic LD <br />N/A <br />N/A <br />Yes/No/NA <br />Slow Flow At Nozzle <br />Yes/No/NA <br />Yes <br />Yes <br />Opening Time <br />(Seconds) <br />3 seconds <br />2 seconds <br />Pass/Fail <br />Pass <br />Pass <br />o nis letter certities that tie annual leak detector tests were performed at the above referenced facility <br />according to the equipment manufacturers procedures and limitations and the results as listed are to my <br />knowledge true and correct. The leak detector test pass/fail is determined using a low flow threshold trip <br />rate of 3 gph at 10 PSI. <br />Technician Signature: 6.�=e& ZJy,w <br />Date: 11/08/2017 <br />CA hc# 588098 1 AZ hc# 095984 ; NV lic# 0049666 1 TX Ric# CR0000041 <br />2 ::, <br />