Laserfiche WebLink
SWRCB, January 2002 <br />0 0 Page _8_ of _8_ <br />9.SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: <br />❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: VISUAL <br />Equipment Resolution: 1/16" <br />Spill Box # 91 FILL <br />Spill Box # 91 <br />VAPOR <br />Spill Box # <br />Spill Box # <br />Bucket Diameter: <br />12" <br />12" <br />Bucket Depth: <br />13.50" <br />14" <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />15 MIN <br />15 MIN <br />Test Start Time: <br />1:00 PM <br />1:00 PM <br />Initial Reading (RI): <br />1.5" FROM TOP <br />1.5" FROM TOP <br />Test End Time: <br />2:00 PM <br />2:00 PM <br />Final Reading (RF): <br />1.5" FROM TOP <br />1.5" FROM TOP <br />Test Duration: <br />1 HR <br />1 HR <br />Change in Reading (RF -RI): <br />0 <br />0 <br />Pass/Fail Threshold or <br />Criteria: <br />NO LOSS <br />NO LOSS <br />Test Result: <br />10 Pass; ❑ Fail <br />0 Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑'Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />VISUAL TEST <br />