Laserfiche WebLink
bp <br /> AUG 14 ?015 <br /> L <br /> EQNVIRONMENTAI <br /> P,j C 4 1 Leak Detector Test Data Sheet <br /> Station # 5450 Date 8/5 2015 <br /> Address 1617 W Fremont <br /> Stockton, CA <br /> Test Information <br /> 2 3 4 5 <br /> Product 87 91 <br /> Manufacturer VR VR <br /> Model 848480 848480 <br /> Full Operating Pressure(psi) 28 30 <br /> Line Bleed Back(ml) NA NA <br /> Trip Time (sec) NA NA <br /> Metering Pressure(psi) NA NA <br /> F/E Holding Pressure (psi) 20 21 <br /> Test Leak Rate(ml/min)(gph) 1 1 <br /> PASS or FAIL P P <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Geftler-Ryan Inc. <br /> Chris San Nicolas <br /> Technician,,, Lic# <br /> Signature <br />