5' G0(214 IAIAk12 k X 0 ' DW T <br /> qW <br /> HOW TO LOCATE THE POSITION OF THE <br /> 71 SO AT 95% TANK CAPACITY , Measuring Stick <br /> The length of the upper tube and the placement of e <br /> the 71 SO valve body determine the shut-off point. <br /> Fallowing the standard instructions for the OPW <br /> 71SO will provide for initial shutoff at 95%. In all <br /> cases,the upper tube length must be a minimum of I + <br /> 6-112"plus the length of the riser pipe. All length f ti <br /> measurements are in inches. } <br /> Riser Pipe <br /> INSTRUCTIONS with Face {A) <br /> Seal Adaptor To Tank <br /> 1.) Find tank ca aci Top(I.D.) (B) <br /> p ty(in gallons)from tank To Tank <br /> calibration chart provided by tank manufacturer. Bottom <br /> 11t bZ7 <br /> 2.)Calculate 95%of capacity. <br /> 1*l 6-112" <br /> 3.)Locate the 95%volume number on the tank <br /> calibration chart. g'2 o t <br /> 4.) Find the dipstick number(X)which corresponds <br /> Figure 1 <br /> to the 95%tank volume. And, find the dipstick <br /> number(Y)which corresponds to�he EXAMPLE <br /> 100°/®volume. n 1.) For an Owens-Corning Model G-3 Fiberglass® <br /> rx Tank Calibration Chart: <br /> 5.)Subtract the dipstick number(X)from the tank Tank Capacity- 10,000 gal., nominal 9,403 gal. <br /> diameter(Y)to find the upper tube reference <br /> number(Z). It NOTE: Use actual capacity only <br /> (Y)-(X)= (Z) $ 2.) 95%of actual tank capacity=0.95 x <br /> 6.)Subtract 2"from (Z)to find the upper tube depth 9403 gal.=$933 gal. <br /> (C)• ? /f3 /t 3.)The closest number which is less than 8933 gal. <br /> (Z)-2"= C Is 8910 gal. Choosing the closest number less <br /> than 95% of actual capacity ensures that the <br /> 7.} Is C less than 6-1l2"? lV ® initial shutoff will occur when the tank is no more <br /> NO Upper tube length is C plus the distance than 95%full. <br /> from the top of the Face Seal Adaptor 4.)The calibration chart reading of 8910 gal. <br /> installed on the riser pipe to the inside,top corresponds to a dipstick measurement of 82". <br /> lip of the storage(A). <br /> Upper Tube Length =C+(A) 5.) Dipstick number(X)=82" <br /> Tank diameter(Y) =92" <br /> YES Upper tube length is 6-112"plus the riser (Y)-(X} (Z) (92"-82"= 10") <br /> (Z)= 10 <br /> pipe measurement(A). <br /> Upper Tube Length=6-1/2"+(A) 7.) (Z)-2"=C (10"-2"=8") <br /> G= 8° <br /> NOTE: You must find the actual tank capacity 7.) Is 8"less than 6-1/2"? <br /> number that correlates to the 6412"+(A) depth <br /> for the station records. This number may also NO Measure the distance from the top of the <br /> be used for the purposes of calibrating an FSA-400 Face Seal Adaptor installed on the <br /> electronic tank level system. riser pipe to the inside,top lip of the storage <br /> tank and obtain measurement(A). <br /> ®Registered T.M.-Owens Corning Fiberglass Corporation Upper tube length=C+(A) <br /> 64 <br />