TAN K AN N U LAR TESTI Kt <br />Tank Manufacturer <br />Xerxes <br />Xerxes <br />Xerxes <br />Tank Capacity <br />10,000 <br />10,000 <br />8.000 <br />Product Stored <br />Is this a multi -compartment tank? <br />No <br />No <br />Brine filled or Dry Annular? <br />Dry <br />Dry <br />Dry <br />(if brine filled, perform no vacuum testing) <br />....... <br />Monitoring system show normal annular? <br />Yes <br />Yes <br />Yes <br />Is water table above tank bottom? <br />X.X <br />Was sensor removed for testing? <br />Yes <br />Yes <br />Yes <br />Was sensor properly replaced after testing? <br />....... ..... <br />Wait time for vacuum to stabilize (hr:min) <br />Xv* 0:20 <br />0:20 <br />Initial vacuum (inches Hg) <br />.... 10 <br />10 <br />10 <br />Pass/Fail threshold (inches Hg/hour) <br />2 <br />2 <br />2 <br />TEST RESULT <br />PASS <br />PASS <br />PASS <br />Replaced sensor in tank #3. <br />Old sensor did not work after reinstalling <br />won comletion of test. <br />0 2002 Walton Engineering, Inc <br />