UNDER DISPENSER CONTAINMENT ( ) TESTING <br /> Test Method By: Manufacturers ! industry Standard v Professional Engr. Other(see below) <br /> Test Method Uses: = Pressure • Vacuum ! Hydrostatic Other(see below) <br /> Measuring Equipment Used: Level Change Indicator (Caldwell system 20011 Walton Engineering) <br /> Description Disp#1/2 Dis 3/4 <br /> UDC manufacturer Bravo Bravo <br /> UDC material Steel Steel <br /> UDC depth (inches) 9" 9" <br /> Height from UDC bottom to highest Bottom Bottom <br /> piping penetration <br /> Height from UDC bottom to lowest Bottom Bottom <br /> electrical penetration <br /> T of shutdown resent Float Float <br /> Condition of UDC prior to testing Dry Dry <br /> Portion of UDC tested Entire Entire <br /> Was sensor removed for testing? N/A N/A <br /> Was sensor properly replaced after testing? N/A N/A <br /> Wait time for water level to stabilize (hr:min) 0:05 0:05 <br /> Depth of water level from UDC bottom (in.) 51 51 <br /> Test start time 11:55 AM 11:57 AM <br /> Test end time 12:25 PM 12:27 PM <br /> Test duration (hr:min) 0:30 0:30 <br /> Change in water level (±0.000 inches) 0.000 0.000 <br /> Pass/Fail threshold (0.005 inches I Hr.) 0.005 0.005 <br /> TEST RESULT PASS PASS <br /> Comments: <br /> © 2003 Watton Engineering,Inc. <br />