Laserfiche WebLink
s <br /> r <br /> Triangle r ' Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: QUIKSTOP #00152 <br /> Tank#: 1 or : 20001408 <br /> Product: Unleaded Regular Test Date: 8/4/03 <br /> Test Method: System 4000 Test Method: R.J.FTA <br /> Capacity: Manufacturer: j <br /> Diameter(in): L/D Model: <br /> Product Level(in): L/D Serial#: <br /> Liquid Volume(Gals): Line Drain Back(ml): <br /> Liquid Percent(%): L/D Trip Time(sec): <br /> Specific Gravity: Holding Pressure(psi): <br /> Coef.of Expansion: Metering Pressure(psi): <br /> Water On Tank(in): L/D Test Rate(gph): <br /> i <br /> Water In Tank(in): L/D Result: <br /> Product Temp. (F): <br /> Head Pressure(psi): <br /> Test Start Time: Test Method: TEI LT-3 <br /> Test End Time: <br /> Pump Brand: Tokhiem <br /> Test Rate(gph): System Type: Pressure <br /> Test Result: Line Pressure(psi): 52 <br /> Line Start Time: 2:45 PM <br /> Test Method: ULLAGE Line End Time: 3:00 PM <br /> UllageVolume(gals.): Line Start Level: 200 <br /> Line End Level: 195 <br /> Ullage Test Time: <br /> Ullage Vacuum(psi): Line Test Rate(gph): -0.006 <br /> Ullage Result: N/A ! Line Test Result: PASS <br /> �vv 0f ��61 <br />