Laserfiche WebLink
4 <br /> SPILL CONTAINER CONTAINMENT TESTING <br /> Test Method By: Manufacturer • Industry Standard • Professional Engr. Other(see below) <br /> Test Method Uses: Pressure Vacuum • Hydrostatic Other(see below) <br /> Measuring Equipment Used: Level Change Indicator (Caldwell System 2001/Walton Engineering) <br /> Description Tank#1 Tank#2 Tank#3 <br /> Spill container manufacturer OPW OPW OPW <br /> Spill container capacity (US gallons) 5 Gallons 5 Gallons 5 Gallons <br /> Spill container depth (inches) 13.00 14.00 14.00 <br /> Product contained Gasoline-87 Gasoline-89 Gasoline-91 <br /> Is Spill container located in a sump? Yes Yes Yes <br /> Does sump have a liquid sensor installed? No No No <br /> Distance between fill adapter and 16" 16" 16" <br /> vapor adapter centers inches <br /> Condition of spill container prior to testing Dry Dry Dry <br /> Portion of spill container tested Entire Entire Entire <br /> Wait time for water level to stabilize (hr:min) 0:20 0:40 0:25 <br /> Depth of water level from bottom (inches) 12.75 13.75 13.75 <br /> Test start time 12:00 PM 12:03 PM 12:45 PM <br /> Test end time 12:30 PM 12:33 PM 1:15 PM <br /> Test duration (hr:min) 0:30 0:30 0:30 <br /> Change in water level (t 0.000 inches) 0.000 0.000 0.000 <br /> Pass/Fail threshold (0.005 inches/%Hr.) 0.005 0.005 0.005 <br /> TEST RESULT PASS PASS PASS <br /> Comments: <br /> © 2003 Walton Engineering,Inc. <br />