Laserfiche WebLink
INVOICE #WC000474 <br />USTest 2000 / P <br />CHAMPION PRECISION TANK TESTING <br />P.O. BOX 13059_ <br />SACRAMENTO CA 95813-3059 <br />TANK STATUS EVALUATION REPORT <br />----------------------------- <br />***** CUSTOMER DATA ***** <br />WATERLOO LIQUOR U -FUEL <br />2512 WATERLOO RD. <br />WATERLOO AND FILBERT ST. <br />STOCKTON,CA. <br />95205 <br />CONTACT: HANK CHER <br />PHONE #: 209-463-4114 <br />TEST DATE: 06/20/96 <br />***** SITE DATA ***** <br />WATERLOO LIQUOR U -FUEL <br />2512 WATERLOO RD. <br />WATERLOO AND FILBERT ST. <br />STOCKTON,CA. <br />95205 <br />CONTACT: HANK CHEA <br />PHONE #: 209-463-4114 <br />***** COMMENT LINES ***** <br />STANDARDSCURRENT EPA D- 3_D <br />THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE THRESHOLD RATE <br />OVER THE PERIOD OF ONE HOUR IS .05 GALLONS. <br />ABOVE STATEMENT N/A FOR THE ULLAGE TEST.MAXIMUM SN:IS +/- 2.0 <br />TANK #1: REG UNLEADED TYPE: STEEL RATE: .004932 G.P.H. LOSS <br />TANK IS TIGHT. <br />TANK #2: SUPER UNLEADED TYPE: STEEL RATE: .006182 G.P.H. GAIN <br />TANK IS TIGHT. <br />TANK #3: PLUS UNLEADED TYPE: STEEL RATE: .028783 G.P.H. GAIN <br />TANK IS TIGHT. <br />OPERATOR: \ a---_ -- SIGNATURE: . ` `--® ® DATE: _ zp wG <br />------ --- ------ <br />