Laserfiche WebLink
CJ <br />S. SECONDARY PIPE TESTING <br />Test Method Developed By: ❑ Piping Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ® Pressure ❑ Vacuum ❑ Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Test reducer boots, Nitrogen and gauges Equipment Resolution: 0.5% of span <br />IMEMEM Sam <br />Piping Run # <br />Piping Run # 87-A Piping Run # 91-A Piping Run # 89-A <br />Diesel <br />Piping Material: Fiberglass Fiberglass Fiberglass Fiberglass <br />Piping Manufacturer: <br />Ameron <br />Ameron <br />Ameron Ameron <br />Piping Diameter: <br />3" <br />3" <br />3" 3" <br />Length of Piping Run: <br />100, <br />100, <br />100, 100, <br />Product Stored: <br />Diesel <br />Gasoline <br />Gasoline Gasoline <br />Method and location of <br />Reducer Boots/Fittings <br />Reducer Boots/Fittings <br />Reducer Boots/Fittings Reducer Boots/Fittings <br />iping-run isolation: <br />Wait time between applying <br />pressure/vacuum/water and <br />10 minutes <br />10 minutes <br />10 minutes 10 minutes <br />starting test: <br />Test Start Time: <br />10:05 am <br />Initial Reading (Rj): <br />5 psi <br />Test End Time: <br />11:05 am <br />Final Reading (RF): <br />5 psi <br />Test Duration: <br />1 hr. <br />Change in Reading (RF-Rj): <br />None <br />Pass/Fail Threshold or <br />Criteria: <br />No detectable Loss <br />No detectable Loss <br />No detectable Loss No detectable Loss <br />Test Result: <br />❑ Pass 0 Fail <br />© Pass ❑ Fail <br />❑ Pass i] Fail ❑ Pass ® Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />DSL, 91-A, 89-A — All failed due to torn test boots. <br />_u <br />Z-s"- <br />ae <br />